Products

Product Introduction



Description:

Aluminum, XLPE Insulated 600V 90°C Dry, Wet, single core and multi cores cable

Technical Data:

Temperature rating of 90°C dry and wet

Sunlight resistant 8 AWG and larger

Lead free

Bare conductors are heat treated after stranding for maximum flexibility

1/0 AWG and larger are CT rated

Code:

RHH/RHW/USE-2, XHHW-2, URD, SER/SEU, MHF, MC

Construction:

Sheath: PVC(Optional)

Armor: Aluminum alloy tape (Optional)

Filler: /

Insulation: Black, sunlight resistant, flame-retardant crosslinked polyethylene (XLPE-FR) meeting the requirements for XHHW-2 per UL 44

Conductor: Compact stranded AA-8000 series aluminum alloy (ACM) per ASTM B801 or B836

Standards:

UL44, UL854, UL1581, NEMA WC70/ICEA S-95-658, NEC Article 310.13

Application:

The cable is rated at 600 volts and 90°C for use in wet and dry locations. XHHW-2 can be used in conduit and other raceways for services, feeders and other applications recognized by the NEC. Sizes 1/0 AWG and larger (4 AWG and larger in green) are cable tray (CT) rated. Sizes 12 - 4/0 AWG meet UL 44 standard for Thermoset-Insulated wires and cables. Also meets NEC Article 310.13

Technical Parameters

Cable Types No. P/N Standard Conductor Type Cores Insulation Bedding & Filler Sheath Rated voltage
UL Cables 1 RHH/RHW/USE-2 UL 44, UL 854 Cu / AA8000 1 XLPE / / 600 V, 1000 V, 2000 V
2 XHHW-2 1
3 URD 2,3,4 XLPE
4 SER/SEU 2,3,4

Keywords:

UL CABLES

Product Message



*Attention: Please ensure accurate information filling and maintain smooth communication. We will contact you as soon as possible