Products

Product Introduction



Description:

1.Flexible Aluminum Conductor Class 5

2.X-HF-110 Insulation

3.HFS-110-TP Sheath (Black-UV stabilized)

Technical Data:

Voltage Rating: 0.6/1kV

Operating Temperature: -40°C to +110°C

Short Circuit Temperature: 250°C for 5 sec.

Code:

ALX2H2

Construction:

Sheath: HFS-110-TP Sheath (Black-UV stabilized)

Armor: /

Filler: /

Insulation: X-HF-110 Insulation

Conductor: Flexible Aluminum

Standards:

AS/NZS 5000.1 Electric Cables-Polymeric insulated. Part 1: For working voltages up to and including 0.6/1kV

AS/NZS 1660.5.6 (Equivalent to IEC 60332-1)

AS/NZS 3808 Insulating and sheathing materials for electric cables

AS/NZS 1660.5.1 (Equivalent to IEC60332-3-24)

AS/NZS 1125 Conductors in insulated electric cables and flexible cords

Application:

Mostly used for buildings and industrial plants where not subject to mechanical damage. Suitable for installation indoor/outdoor, enclosed in conduit, and in underground duct.

Technical Parameters

Nominal Cross Section Conductor Diameter Insulation Thickness Approx. Overall Diameter Min. Bending Radius (mm) Approx. Weight
(mm²) (mm) (mm) (mm) During Installation After Installation (kg/km)
35 8.6 0.9 13.1 144 86 229
50 10.4 1.0 15.3 168 101 289
70 11.7 1.1 16.9 186 112 386
95 13.5 1.1 18.8 207 124 477
120 15.4 1.2 21.0 231 139 590
150 16.4 1.4 22.5 248 149 725
185 18.3 1.6 25.0 275 165 883
240 20.8 1.7 27.9 307 184 1094
300 23.2 1.8 30.7 338 203 1330
400 29.2 2.0 37.5 413 248 1737
500 32.2 2.2 41.2 453 272 2236
630 36.4 2.4 46.1 507 304 2906

Keywords:

SDI-110-AF

Product Message



*Attention: Please ensure accurate information filling and maintain smooth communication. We will contact you as soon as possible